Section 8 Parameters
CH
Standby Sequence Reset
Function
Setting
Reference
Reference
8-78
rest
• Use this parameter to select the condition for restarting the standby
sequence after it has been canceled.
• Conditions A:
• At the start of operation (including after turning ON power),
• When the alarm value (alarm upper or lower limit) is changed,
• When the input correction (Input Value 1 for Input Correction,
Input Correction 1, Input Value 2 for Input Correction, or Input
Correction 2 parameter) is changed,
• When the SP of the current segment is changed (including
changing the fixed SP in Fixed SP Mode),
• When program is started (including when the program is started
for program repeats or links), or
• When the segment is changed (including when an advance is
executed).
• Condition B: Power ON
• The following example shows operation using a lower-limit alarm
with standby sequence.
Alarm point
(after change)
Alarm point
Alarm output: Conditions A
Alarm output: Condition B
• After changing the standby sequence reset setting, a software reset
must be executed or the power turned OFF and ON to make the
change take effect.
Setting range
a: Condition A
b: Condition B
● Related Parameters
Alarm
Type (Alarm Setting Level) (P. 8-75)
Alarm
Latch (Alarm Setting Level) (P. 8-76)
= With standby sequence
Condition A only
SP changed
O : Standby sequence
Condition A only
O : Standby sequence
Unit
Default value
a: Condition A
l.3
Alarm Types 1 to 4
Alarm hysteresis
off point
reset point