Auxiliary Output
Open in Alarm
: 1 to 10)
Function
Setting
Reference
Reference
sb*n
• These parameters are used to select the output state of auxiliary
outputs 1 to 10.
• When "Close in alarm" is selected, the state of the alarm output
function is output without change. When "Open in alarm" is selected,
the state of the output function is inverted before output. The relation
between the alarm output function, alarm output, and operation
indicator is shown below.
Auxiliary
Set value
output function
ON
Close in Alarm
OFF
ON
Open in Alarm
OFF
Setting range
n-o: Close in alarm
n-c: Open in alarm
● Related Parameters
Alarm Set
Alarm Value
Alarm Set
Alarm Upper limit
Auxiliary Output
Assignment (Control Initial Setting 2 Level)
(P. 8-67)
Alarm
Type (Alarm Setting Level) (P. 8-75)
Alarm
Hysteresis (Alarm Setting Level) (P. 8-77)
Standby Sequence Reset (Alarm Setting Level) (P. 8-78)
Alarm SP Selection (Expansion Control Setting Level) (P. 8-97)
8.14 Alarm Setting Level (l.3)
Auxiliary
output
ON
ON
OFF
OFF
OFF
ON
ON
OFF
Unit
Default value
n-o: Close in alarm
(Alarm Set Setting Level) (P. 8-37)
(Alarm Set Setting Level) (P. 8-38)
l.3
Operation
indicator
8-79