● Operation at
Potentiometer
Input Error
The Operation at Potentiometer Input Error parameter is used to select
the operation to perform if an error occurs with the potentiometer
during closed control. The selections are to stop control or switch to
floating control and continue.
Potentiometer errors are not detected if the O or C lines
are disconnected on the potentiometer. This function,
Important
i.e., the option of stopping control or switching to float-
ing control, is not supported in such cases.
4.6 Selecting the Control Mode
4-19