Setting
Reference
Reference
CH
PV Decimal Point Display
This parameter can be used to not show the digits of the PV below the decimal point.
Function
Setting
Reference
Reference
Parameter
Setting range
Remote SP
Temperature:
Lower limit of sensor set-
Upper Limit
ting range to upper limit of
sensor setting range
Analog:
(Larger of 19999 and dis-
Remote SP
play value equivalent to
Lower Limit
lower input limit) to
(smaller of 99999 and dis-
play value equivalent to
upper input limit)
* According to setting of the Input Type parameter.
● Related Parameters
Input
Type (Input Initial Setting Level) (P. 8-50)
Input
Temperature Units (Input Initial Setting Level) (P. 8-51)
Control Mode (Control Initial Setting Level) (P. 8-58)
SP Upper Limit and SP Lower Limit (Control Initial Setting Level)
(P. 8-57)
Note:When the remote SP input is set to a temperature input, be sure
to set the input type of the main input to the same setting as the
input type of remote SP input.
If the remote SP input is set to a temperature input and the upper
and lower limits of the remote SP are not the same as the upper
and lower limits of the sensor setting range of the input type of
remote SP input, it will not be possible to obtain a correct remote
SP value.
pvdp
• If this parameter is turned OFF, the digits of the PV below the
decimal point are not shown. When turned ON, the digits below the
decimal point are shown according to the input type setting.
Setting range
off : OFF
on : ON
● Related Information
Input
type (Input Initial Setting Level) (P. 8-50)
8.11 Input Initial Setting Level (l.0)
Unit
Default value
EU
1300.0
EU
200.0
Temperature input
Unit
Default value
on: ON
l.0
8-53