CH
Cooling Coefficient
Function
Setting
Reference
Reference
CH
Dead Band
Function
Setting
c-sc
Heating/cooling control, Advanced PID control
If there is a large difference in the heating and cooling characteristics
of the object and satisfactory control is not possible using the same
PID constants, the heating P (proportional band) can be multiplied by a
coefficient for use in cooling control.
• The cooling P in heating/cooling control is obtained using the
following equation and the coefficient is set accordingly.
Cooling P = Cooling coefficient
Setting range
0.01 to 99.99
● Related Parameters
PID Proportional Band (PID Setting Level) (P. 8-40)
c-db
This parameter sets an output dead band for heating/cooling control. A
negative value can also be set to create an overlap band.
• Set an area centered on the SP where the control amount is 0
during heating/cooling control.
Setting range
19.99 to 99.99
8.5 Adjustment Level (l.adj)
l.adj
(Proportional band 0.00)
P (heating proportional band)
Unit
Default value
None
1.00
l.adj
Heating/cooling control
Unit
Default value
%FS
0.00
8-25