6.6 Write to Variable Area

Write to a variable area by setting the required data in the following FINS-mini command text format.
Command
Response
FINS-mini Command Text
Variable
Write start
MRC
SRC
type
address
"01"
"02"
2
2
2
4
Data name
Specify the Write to Variable Area FINS-mini com-
MRC/SRC
mand.
Variable type
Specify the variable type.
Write start address
Specify the first address to write.
Bit position
Not used on the E5AR-T/ER-T. Specify "00."
Specify the number of variables to be written (max.
Number of elements
of 25 (H'18)). Not needed for a compound write.
Write data
Enter the data to be written.
FINS-mini Response Text
Response code
MRC
SRC
(MRES/SRES)
"01"
"02"
2
2
4
Data name
MRC/SRC
FINS-mini command text is returned here.
Response code
Result of execution of the command.
Response Codes
Response
Error name
code
Command length
"1002"
too short
"1101"
Area type error
Number of ele-
"1003"
ments/data num-
ber do not agree
"1100"
Parameter error

6.6 Write to Variable Area

Number of
Bit position
elements
"00"
2
"0001" to "0018"
4
Description
Description
Description
The command is too short.
Incorrect variable type.
The specified number of elements does
not agree with the actual number of data
elements.
Specified bit position is not "00."
Write data was outside of setting range.
Write data
6-11