Advertisement

CH
Remote SP Monitor
Function
Monitor
Reference
Reference
CH
MV Monitor (Heating)
Function
Monitor
rsp
Program SP or Fixed SP Mode with remote SP or
• This parameter is used to monitor the remote SP while in Program
SP or Fixed SP Mode.
• In Remote SP Mode, the remote SP can be monitored on Display
No. 2 of the Present Value (PV)/Present Set Point display.
Monitor range
Remote SP lower limit to remote SP upper limit
The SP limits are in effect.
● Related Parameters
Present Value (PV)/Preset Set Point (Operation Level) (P. 8-9)
SP Mode (Adjustment Level) (P. 8-24)
Remote SP Upper Limit and Remote SP Lower Limit (Input Initial
Setting Level) (P. 8-52)
Control Mode (Control Initial Setting Level) (P. 8-58)
o
This parameter monitors the heating MV during operation.
• This parameter monitors the MV of standard control and the heating
MV of heating/cooling control.
Control
Standard
5.0 to 105.0
Heating/
0.0 to 105.0
cooling
8.3 Operation Level ( )
Coordinated operation with fixed SP
Unit
EU
Standard control or heating/cooling control
Monitor range
Unit
%
%
8-13