■ AT Execute

Command
This command is used to start or reset control.
This command can be used in setting area 0.
If "All" is selected for the channel, only the channels that are enabled
will be affected by this command.
To use this command, the communications writing function must be
enabled using the Communications Writing operation command.
MRC
SRC
Response code
"30"
"05"
"0000"
Response Codes:
The response for a normal end is shown above. For the
response codes, refer to 6.7 Operation Commands (P. 6-13).
Instruction
Related
MRC
SRC
code
information
"30"
"05"
"03"
Related
information
Ch
00: Current PID set number
"00" to "08"
1
01 to 08: PID set number 1 to 8
10: Current PID set number
"10" to "18"
2
11 to 18: PID set number 1 to 8
20: Current PID set number
"20" to "28"
3
21 to 28: PID set number 1 to 8
30: Current PID set number
"30" to "38"
4
31 to 38: PID set number 1 to 8
F0: Current PID set number
"F0" to "F8"
All
F1 to F8: PID set number 1 to 8
This command executes AT. On the E5AR-T/ER-T, the PID set
number must be specified when executing AT.
To specify the current PID set number (the PID set currently being
used for operation), set the lower byte of the related information to 0.
This command is used in setting area 0. An operation error will occur if
it is used in setting area 1. An operation error will also occur in the
following cases:
• If the Run/Reset parameter is set to "Reset" for the
specified channel
• If the Auto/Manual parameter is set to "Manual" for the
specified channel
To use this command, the communications writing function must be
enabled using the Communications Writing operation command.