8.18 Expansion Control Setting Level (l.exc)
mant
mani
These parameters are used to specify how the MV is output when
switching from Auto Mode to Manual Mode.
• When "Hold MV" is selected, the MV at the time of switching is held,
after which it can be changed using the Manual MV parameter
(Operation Level).
• When "Output default value" is selected, the value specified in the
Manual MV Initial Value parameter is used. This can then be
changed using the Manual MV parameter (Operation Level).
Examples of how the MV changes using the two methods are shown
below.
MV
Auto mode
Manual mode
"MV hold"
Parameter
Manual Output
MV hold:
Default value output: init
Method
5.0 to 105.0
Manual MV Initial
(Standard)
Value
105.0 to 105.0
(Heating/cooling)
● Related Information
4.13 Manual Operation (P. 4-47)
● Related Parameters
Manual MV (Operation Level) (P. 8-7)
Standard Control Model
MV
Time
Auto mode
"Initial value output"
Setting range
Unit
hold
%
l.exc
Manual MV
Initial Value
Time
Manual mode
Default value
hold
0.0
8-101