Section 5 Functions and Operations
● Transfer Output
Scaling
5-48
• Scaling of the output value can be performed using Transfer Output
Upper Limit and Transfer Output Lower Limit parameters. The upper-
limit can be set to a smaller value than the lower limit to perform
reverse scaling. The scale can be enlarged using the width between
the upper and lower limits specified in the parameters. The following
diagram shows an example of scaling the heating MV.
Transfer output
(mA)
Reverse scaling
20
4
0
Upper limit: 0
Lower limit: 100
• If the Input Type, Scaling Input Value 1 or 2, SP Upper and Lower
Limit, or Temperature Unit parameter is changed, the Transfer
Output Upper Limit and Transfer Output Lower Limit parameters will
be returned to the upper and lower limits of the setting range.
• If an input error occurs when the transfer output assignment is set to
"PV," the transfer output changes to the upper limit and it changes to
the lower limit for reverse scaling.
Before change
After changing
upper limit
Upper and lower limits
Upper and lower limits of transfer scaling
Display
Parameter
Control/Transfer
out.
Output 1 to 4
Assignment
trh.
Transfer Output 1
to 4 Upper Limit
and
trl.
Transfer Output 1
to 4 Lower Limit
: 1 to 4
Transfer output
(mA)
Scaling enlargement
20
4
MV (%)
0
Lower limit: 10
Upper limit: 80
SP limit
Transfer scaling range
A
Upper limit
changed
from A to B.
B
Level
(Display No. 3)
Control Initial
Specify Control/
Setting 2 (l.2)
Transfer Output
Control Initial
Transfer Output
Setting 2 (l.2)
Scaling
MV (%)
100
SP
SP
Use