Section 6 CompoWay/F Communications
Response
6-20
Variable
Address
type
"0000" to "004F"
"0100" to "014F"
"C5" to "CB"
"D8" to "D9"
"0200" to "024F"
"0300" to "034F"
"0000" to "003B"
"0100" to "013B"
"CC" to "D3"
"0200" to "023B"
"0300" to "033B"
Multiple monitor values or set values can be read by sending a single
command. Up to 20 items can be read even if the addresses are not
consecutive.
To specify variable types and addresses, refer to Appendix Setting
Lists (P. A-6). The upper limit of an address depends on the variable
type.
This command can be used in both setting area 0 and setting area 1.
If an area type error or a set value error occurs in any of the data being
read, no data will be read.
MRC
SRC
Response code
Variable type
"01"
"04"
"0000"
Response Codes:
The response for a normal end is shown above. For the
response codes, refer to 6.5 Read from Variable Area (P. 6-10).
Parameters
Ch
Description
1
2
Parameters in setting area 0
3
4
1
2
Parameters in setting area 1
3
4
Data
Type
Monitor value/Set value
Variable type
Type
Monitor value/Set value
Data