Section 8 Parameters
Event Input
Assignment
( : 1 to 10)
Function
Setting
Reference
Reference
8-66
Oev.*
• Use these parameters to assign event input functions.
Setting range
Disable (0)
Communications Writing OFF/ON (1)
Channel 1 Program No. (bit 0, weight 1) (2)
Channel 1 Program No. (bit 1, weight 2) (3)
Channel 1 Program No. (bit 2, weight 4) (4)
Channel 1 Program No. (bit 3, weight 8) (5)
Channel 1 Program No. (bit 4, weight 16) (6)
Channel 1 Program No. (bit 5, weight 32) (7)
Channel 1 Program No. (bit 0, weight 10) (8)
Channel 1 Program No. (bit 2, weight 20) (9)
Channel 1 Run (ON)/Reset (OFF) (10)
Channel 1 Run (OFF)/Reset (ON) (11)
Channel 1 Auto (OFF/Manual (ON) (12)
Channel 1 Program SP (OFF)/Remote SP (ON) (13)
Channel 1 Remote SP (OFF)/Fixed SP (ON) (14)
Channel 1 Program SP (OFF)/Fixed SP (ON) (15)
Channel 1 Program SP (16)
Channel 1 Remote SP (17)
Channel 1 Fixed SP (18)
Channel 1 Hold (ON)/Hold clear (OFF) (19)
Channel 1 Advance (20)
Channel 1 Back (21)
Similarly
Channel 2 (22 to 41)
Channel 3 (42 to 61)
Channel 4 (62 to 81)
• If the same setting is selected for different Event Input Assignment
parameters, the event input for which ON/OFF is determined last will
be effective. When the power is turned ON and the same program
number assignment is repeated, the event input with the higher
number is given priority.
When the control mode is set to cascade control, assign
the following channel operation commands:
• CH2 Run/Reset (31)
Important
• CH2 Auto/Manual (32)
• CH2 SP Mode (Remote SP/Fixed SP) (34)
(cascade open/close)
● Related Information
5.8 Using Event Inputs (P. 5-39)
l.2
Default
Unit
value
0