Response
■ Software Reset
Command
Response
■ Move to Setting Area 1
Command
Slave
Function
Write start
Operation
address
code
address
code
H'06
H'00
H'00
H'05
1
1
2
The response for a normal end is shown above. For information on
error responses, refer to 7.7 Operation Commands (P. 7-15).
Slave
Function
Write start
Operation
address
code
address
code
H'06
H'00
H'00
H'06
1
1
2
A software reset causes the same operation as turning the power OFF
and ON.
This command can be used in both setting area 0 and setting area 1.
To use this command, the communications writing function must be
enabled using the Communications Writing operation command.
Slave
Function
Write start
Operation
address
code
address
code
H'06
H'00
H'00
H'06
1
1
2
The response for a normal end is shown above. For information on
error responses, refer to 7.7 Operation Commands (P. 7-15).
Slave
Function
Write start
Operation
address
code
address
code
H'06
H'00
H'00
H'07
1
1
2
Use this command to move to setting area 1.
The command is used in setting area 0. Nothing happens if the
command is used in setting area 1.
If the command is used when the Initial Setting Protection parameter is
set to 2 (Disable Move to Input Initial Setting Level), an operation error
will occur.
To use this command, the communications writing function must be
enabled using the Communications Writing operation command.
7.9 Commands and Responses
Related
information
CRC-16
H'00
2
2
Related
information
CRC-16
H'00
2
2
Related
CRC-16
information
H'00
2
2
Related
CRC-16
information
H'00
2
2
7-29