Section 8 Parameters
CH
Wait Mode
Function
Setting
Reference
Reference
8-96
wt-m
This parameter is used to specify the Wait operating mode.
• Wait at Segment End
When this set value is selected, the program will not move to the
next segment when one segment is completed unless the difference
(deviation) between the PV and SP are within the wait band. The
program will move to the next segment as soon as the deviation is
within the wait band.
• Always Wait
The difference (deviation) between the PV and SP are constantly
compared during program operation. If the deviation is not within the
wait band the SP is held at the point that the deviation went outside
the wait band and the program does not move on. The program
moves on as soon as the deviation enters the wait band.
Setting range
send: Wait at Segment End
all: Always Wait
● Related Information
Wait in 5.7 Program Operation Functions (P. 5-32)
● Related Parameters
Wait Band Upper Limit and Wait Band Lower Limit (Program Setting
Level) (P. 8-20)
Unit
Default value
send: Wait at Segment End