Section 6 CompoWay/F Communications

■ Communications Writing

Command
Response

■ Run/Reset

Command
6-26
Instruction
Related
MRC
SRC
code
information
"30"
"05"
"00"
Related
information
"00"
Communications Writing Disabled
"01"
Communications Writing Enabled
This command is used to enable or disable the communications
writing function. It changes the setting of the Communications Writing
parameter.
When the communications writing function is disabled, communica-
tions cannot be used to write set values or send operation commands,
such as the Run/Reset operation command.
The default setting is "Communications Writing Disabled."
This command can be used in both setting area 0 and setting area 1.
MRC
SRC
Response code
"30"
"05"
"0000"
Response Codes:
The response for a normal end is shown above. For the
response codes, refer to 6.7 Operation Commands (P. 6-13).
Instruction
Related
MRC
SRC
code
information
"30"
"05"
"01"
Description
Related
information
Ch
"00"
1
"01"
"10"
2
"11"
"20"
3
"21"
"30"
4
"31"
"F0"
All
"F1"
Description
Control state
Run
Reset
Run
Reset
Run
Reset
Run
Reset
Run
Reset