Section 4 Settings Required for Basic Control
● Number of
Segments Used
● Segment Set Point
and Segment Time
4-24
Setting of Number of
Segments parameter
8
12
16
20
32
• The Number of Segments Used parameter is used to set the
number of segments used for a specified program.
• The default is 8. The following table shows the setting ranges.
Setting of Number of
Segments parameter
8
12
16
20
32
• Once the program has been executed for the number of segments
set for the Number of Segments Used parameter, the program will
be in operation completed status. If the setting of the Number of
Segments Used parameter is changed to a value smaller than the
segment currently being executed in the program, the program will
immediately change to operation completed status.
• The Segment Set Point and Segment Time parameters are used to
set one segment of a program. The present SP is determined by
using the SP of the previous segment as the start point and the SP
of the current segment as the end point. A straight line is drawn
between these two points and the present SP is the point on that
line where the current segment time has elapsed.
• The Segment Time parameter can be set to between 0.00 and 99.59
(hours. minutes or minutes. seconds) or between 0.00.0 and 99.59.9
(minutes. seconds.tenths of seconds). The default is 0.00 or 0.00.0.
• The first segment is a soak segment. To start from a ramp, set the
Segment Time parameter for segment 1 to 0 to create a program
that starts from segment 2 (when the Operation at Reset parameter
is set to "Control Stop").
Setting range
1 to 32
1 to 20
1 to 16
1 to 12
1 to 8
Setting range
1 to 8
1 to 12
1 to 16
1 to 20
1 to 32