Omron E5AR-T User Manual page 268

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

CH
Input Value 1 for Input Correction
Input Correction 1
Input Value 2 for Input Correction
Input Correction 2
Function
Setting
Reference
Reference
isi.1
iss.1
isi.2
iss.2
The input can be corrected at any two points.
These parameters are used to set correction values (Input Correction
1 and Input Correction 2 parameters) for any two points (Input Value 1
for Input Correction and Input Value 2 for Input Correction parameters)
for two-point correction.
PV
Input Correction 2
1,300
After correction
Before
correction
Input Correction 1
200
200
0
Input Value 1
Input Value 2
for Correction
for Correction
Parameter
Input Value 1 for Input
Correction
Input Correction 1
Input Value 2 for Input
Correction
Input Correction 2
*1 The decimal point position depends on the input type.
*2 If the input type is changed, the default values of the input value for
input calibration will change to the upper and lower-limits of the
input range of the sensor type being used.
● Related Parameters
Input
Type (Input Initial Setting Level) (P. 8-50)
8.5 Adjustment Level (l.adj)
Input
1,000
1,300
Setting range
Unit
19999 to 99999
EU
*1
199.99 to 999.99
EU
19999 to 99999
EU
*1
199.99 to 999.99
EU
l.adj
Default value
200.0
0.00
1300.0
0.00
8-31