Section 4 Settings Required for Basic Control
Number of Segments
25.0
150.0
01.01
i1-t
2
l.0
o1-t
0
l.1
snum
16
8
l.1
Number of Segments Used
25.0
100.0
01.01
prg.n
1
01.00
prg.n
2
02.00
4-26
Use the following procedure to set the Number of Segments
parameter to 8 (thus setting the number of programs to 32).
(1) Hold down the L Key for at least 3 seconds to move from the Operation
Level to the Input Initial Setting Level.
(2) In the Input Initial Setting Level, Display No. 3 will show l.0.
Press the L Key for less than 1 second to move to the Control Initial
Setting Level.
(3) In the Input Initial Setting Level, Display No. 3 will show l.1.
Press the M Key repeatedly (less than 1 second each time) to select the
Number of Segments parameter.
(4) Press the D to set the Number of Segments parameter to 8.
Use the following procedure to set the Number of Segments Used
parameter to 4.
(1) Hold down the L Key for less than 1 second to move from the Operation
Level to the Program Setting Level.
(2) The Program Editing parameter will be displayed in the Program
Setting Level. Select the number of the program to be edited. For
example, to change the Number of Segments Used parameter for
program 2, use the D Key to select 2.