Section 8 Parameters
Input
Type
( : 1 to 4)
Function
Setting
Reference
Reference
8-50
i*-t.
• These parameters are used to set the sensor types.
• If these parameters are changed, the SP limit settings are returned
to the Initial settings. Reset the SP Upper Limit and SP Lower Limit
parameters as necessary.
• Refer to the following table to set the parameters. The default setting
is shaded.
Set
Input
value
type
0
Pt100(1)
200.0 to 850.0
1
Pt100(2)
150.00 to 150.00
2
K(1)
200.0 to 1300.0
3
K(2)
20.0 to 500.0
4
J(1)
100.0 to 850.0
5
J(2)
20.0 to 400.0
6
T
200.0 to 400.0
7
E
0.0 to 600.0
8
L
100.0 to 850.0
9
U
200.0 to 400.0
10
N
200.0 to 1300.0
11
R
0.0 to 1700.0
12
S
0.0 to 1700.0
13
B
100.0 to 1800.0
14
W
0.0 to 2300.0
15
Depends on scaling
4 to 20 mA
One of the following ranges is dis-
16
0 to 20 mA
played depending on the scaling:
17
1 to 5V
19999 to 99999
18
0 to 5V
1999.9 to 9999.9
199.99 to 999.99
19
0 to 10V
19.999 to 99.999
1.9999 to 9.9999
Set the input type switch of each input to match the Input Type
parameter of the corresponding input. The default setting is 2 (TC.PT).
● Related Parameters
Input
Temperature Units (Input Initial Setting Level) (P. 8-51)
SP Upper Limit and SP Lower Limit (Control Initial Setting Level)
(P. 8-57)
Setting range
(°C)
(°F)
300.0 to 1500.0
199.99 to 300.00
300.0 to 2300.0
0.0 to 900.0
100.0 to 1500.0
0.0 to 750.0
300.0 to 700.0
0.0 to 1100.0
100.0 to 1500.0
300.0 to 700.0
300.0 to 2300.0
0.0 to 3000.0
0.0 to 3000.0
300.0 to 3200.0
0.0 to 4100.0
l.0
Input type
switch
TC.PT
TC.PT
I N
TYPE
ANALOG
ANALOG
TC.PT
I N
TYPE
ANALOG