Outputs - Omron E5AR-T User Manual

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

● A wide Variety of
Control Modes and
Functions

■ Outputs

● Multi-output
Function
● High Resolution
● Control Period
1.1 Main Features of the E5AR-T and E5ER-T
• PID sets can be selected not only by directly specifying the PID set
number in a program, but they can also be selected automatically
according to the present value, deviation, or set point.
• Coordinated operation is possible with one Digital Controller for
models with 2 or 4 input channels, eliminating the need for slave
adjusters.
• Position-proportional Control Models support floating control or
closed control. Floating control allows position-proportional control
without a potentiometer.
• Multi-outputs enable using either current outputs or voltage outputs
(pulses).
• Resolution of Current Outputs
0 to 20 mA: Approx. 54,000
4 to 20 mA: Approx. 43,000
• The control period can be set as short as 0.2 seconds, allowing
precise time-proportioning control for voltage output pulses.
1-3