Section 6 CompoWay/F Communications
Response
6-22
Variable
Address
type
"0000" to "003B"
"CC"
"CD"
"0100" to "013B"
"CE"
"CF"
"D0"
"0200" to "023B"
"D1"
"D2"
"0300" to "033B"
"D3"
This command is used to write set values. The number of elements
can be set from 2 to 24 to write set values at consecutive addresses.
To specify an address, refer to Appendix Setting Lists (P. A-6).
Parameters in setting area 1 can be written from setting area 1. An
operation error will occur if parameters are written from setting area 0.
To use this command, the communications writing function must be
enabled using the Communications Writing operation command.
To store the set values for Operation, Program Setting, Adjustment,
Adjustment 2, Alarm Set Setting, PID Setting, Time Signal Setting, or
Approximation Setting Level in EEPROM, select "Backup Mode" and
execute the RAM Write Mode command. If "Backup Mode" is not
selected, the set values will not remain in memory when the power is
turned OFF. For more information on the above levels, refer to 4.1
Setting Levels and Key Operations (P. 4-2).
MRC
SRC
Response code
"01"
"02"
"0000"
Response Codes:
The response for a normal end is shown above. For the
response codes, refer to 6.6 Write to Variable Area (P. 6-11).
Parameter
Ch
Description
1
Parameters in Setting Area 1
Input Initial Setting Level
Control Initial Setting Level
2
Control Initial Setting 2 Level
Alarm Setting Level
3
Display Adjustment Level
Communications Setting Level
Advanced Function Setting Level
4
Expansion Control Setting Level