Section 8 Parameters
CH
SP Mode
Function
Operation
Reference
Reference
CH
Fixed SP
Function
Setting
Reference
Reference
8-24
spmd
• Use this parameter to select the SP mode.
• In Program SP Mode, the SP corresponding to the set program will
be used for control. In Remote SP Mode, the remote SP specified by
an external input (e.g., 4 to 20 mA) will be the SP. In Fixed SP Mode,
the value set for the Fixed SP parameter will be used as the SP.
• The default setting for this parameter is "Program SP Mode". For
coordination operation CH2 to CH4 and the cascade control
secondary side (CH2), the default is Remote SP Mode.
Furthermore, if the Operation at Reset parameter is set to "Fixed
Control", all control will be in Fixed SP Mode except for the cascade
control secondary side (CH2).
• Use the
U and D Keys
Mode. Select rsp (Remote SP) for Remote SP Mode. When Fixed
SP Mode is selected, the RSP indicator lights. Select fsp (Fixed
SP) for Fixed SP Mode. When Fixed SP Mode is selected, the FSP
indicator lights.
• When cascade control is used, cascade open (secondary loop
independent control) takes place when the SP mode of channel 2 is
Fixed SP Mode, and cascade closed (cascade control) takes place
when the SP mode is Remote SP Mode.
• For coordinated operation, channels 2 to 4 will be in Remote SP
Mode.
● Related Information
SP Modes in 5.7 Program Operation Functions (P. 5-31)
● Related Parameters
Control Mode (Control Initial Setting Level) (P. 8-58)
fsp
• This parameter is used to set the SP used in Fixed SP Mode.
Setting range
Set Point Lower Limit to Set Point Upper Limit
● Related Information
SP Modes in 5.7 Program Operation Functions (P. 5-31)
● Related Parameters
SP Mode (Adjustment Level) (P. 8-24)
Operation at Reset parameter set to
"Stop Control" or Control Mode parameter
set to "Remote SP" or "Proportional Control"
to select psp (Program SP) for Program SP
Unit
EU
l.adj
l.adj
Default value
0