Input type 0
p 20.1
04888
l.cal
Input type 1
p 40.1
19c86
l.cal
str.i1
no
l.cal
7. Press the M Key. The display at the left will appear.
Set the 6-dial resistance box as follows:
• Input type 0: 20
• Input type 1: 40
8. Wait until the count on Display No. 2 is sufficiently stable and then press
the D Key. This tentatively registers the calibration data at this point.
9. Press the M Key. The display at the left will appear. This display will not
appear if all of the required data has not been tentatively registered.
Press the U Key. Display No. 2 will show yes. Two seconds after the Key
is released or when the M is pressed, the tentatively registered calibration
data will be stored in EEPROM. If you do not wish to save the data in
EEPROM, press the M Key instead of the U Key.
• For a Controller with more than one input, connect as explained in step 2
and repeat steps 5 to 9.
• If linear current output is selected, continue with the procedure in 9.6
Output Calibration (P. 9-12).
10. Turn OFF the power to leave Calibration Mode.
9.5 Resistance Thermometer Calibration
9-11