Omron E5AR-T User Manual page 154

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

● Fixed SP
● Hold (ON)/Clear
Hold (OFF)
● Advance
• When the event input is ON, the fixed SP (FSP) is used as the SP.
The event input must be reset before this function can be activated
again.
• The Fixed SP function creates an operation command that applies
to one specific channel.
• Operation is as follows based on the ON/OFF status of the event
input:
Event input
• When the event input is ON, the program is on hold and this status is
held until the event input changes to OFF.
• The Hold (ON)/Clear Hold (OFF) function creates an operation
command that applies to one specific channel. During coordinated
operation, however, the operation command applies to all channels.
• This function is enabled only during program operation.
• Operation is as follows based on the ON/OFF status of the event
input:
Event input
• When the event input is ON, the segment is advanced to the
beginning of the next segment. The event input must be reset before
this function can be activated again.
• The advance function creates an operation command that applies to
one specific channel. During coordinated operation, however, the
operation command applies to all channels.
• This function is enabled only during program operation.
• Operation is as follows based on the ON/OFF status of the event
input:
Event input
5.8 Using Event Inputs
Description
Fixed SP Mode
Description
Clear Hold Mode
Hold Mode
Description
Advance Mode
5-45

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5er-t

Table of Contents