CH
Control Period (Heating)
Control Period (Cooling)
Function
Setting
Reference
Reference
CH
Position-proportional Dead
Band
Function
Setting
Reference
Reference
cp
c-cp
• These parameters set the output periods. When setting these
parameters, take controllability and product life (if the connected
device is a relay) into consideration.
• The Control Period (Heating) parameter is used for standard control.
• For heating/cooling control, control periods can be set separately for
heating and cooling.
Parameter
Control Period
0.2 to 99.0
(Heating)
Control Period
0.2 to 99.0
(Cooling)
● Related Parameters
PID Proportional Band (PID Setting Level) (P. 8-40)
db
• This parameter sets the output hold interval (the interval between
switching the open output and close output ON and OFF) during
position-proportional control.
Data range
0.1 to 10.0
● Related Parameters
Open/Close Hysteresis (Adjustment Level) (P. 8-28)
8.5 Adjustment Level (l.adj)
Setting range
Unit
s
s
Position-proportional Control Model
Unit
%
2.0
l.adj
Default value
20.0
20.0
l.adj
Default value
8-27