Section 5 Functions and Operations
● Initial Setting
Protection
Initial Setting Protection
icpt
0
l.prt
● Setting Change
Protection
Setting Change Protection
wtpt
off
l.prt
● PF Key Protection
PF Key Protection
pfpt
off
l.prt
5-24
Initial Setting Protection restricts access to the Input Initial Setting,
Control Initial Setting, Control Initial Setting 2, Alarm Setting, Display
Adjustment, and Communications Setting Levels.
Set
Move to Input Initial
value
Setting Level
Enabled
Move to Advanced Func-
0
tion Setting Level param-
eter is displayed.
Enabled
Move to Advanced Func-
1
tion Setting Level param-
eter is not displayed.
2
Prohibited
• When the Initial Setting Protection parameter is set to 2, nothing
happens when the Level Key is held down to move to Input Initial
Setting Level from Operation Level, Program Setting Level,
Adjustment Level, Adjustment 2 Level, Alarm Set Setting Level, PID
Setting Level, Time Signal Setting Level, Approximation Setting
Level, or Monitor Item Level. (The flashing display to indicate
movement to another level also does not appear.)
• The default setting is 0.
Setting Change Protection prevents use of the
Set
value
OFF
Keys can be used to change settings.
Keys cannot be used to change settings. (However, settings
ON
can be changed in Protect Level.)
• The default setting is OFF.
PF Key Protection prevents use of the PF1/PF2 Keys.
Set
value
OFF
PF1/PF2 Keys are enabled.
PF1/PF2 Keys are disabled.
ON
(Prohibits use as a function key or a channel key.)
• The default setting is OFF.
Move to Control Initial Setting,
Control Initial Setting 2, Alarm
Setting, Display Adjustment, or
Communications Setting Level
Enabled
Enabled
Prohibited
U and D Keys
Description
Description
.