Section 4 Settings Required for Basic Control

■ Settings

Setting ON/OFF Control
(Proportional Band = 0.00)
25.0
100.0
01.01
d.pid
1
l.pid
1.p
10.00
l.pid
Setting the Hysteresis
25.0
100.0
01.01
hys
0.10
l.adj
hys
2.00
l.adj
4-32
To perform ON/OFF control, the SP, Proportional Band, and Hysteresis
(Heating) parameters must be set.
To ON/OFF control and an hysteresis (heating) of 2.00% FS, set the
Proportional Band parameter to 0.00 in PID Setting Level to select ON/
OFF control.
1. Press the L Key repeatedly (less than 1 second each time) to move from
the Operation Level to the PID Setting Level.
2. The PID Selection parameter is displayed in the PID Setting Level. If a PID
set number will not be used, use the default setting (1). If a PID set number
will be used, select the PID set number for the desired control.
3. .Press the M Key to display the Proportional Band parameter. Use the U
and D Keys to set the value to 0.00
4. Press the L Key repeatedly (less than 1 second each time) to return to the
Operation Level.
Set the Hysteresis (Heating) parameter to 2.00 in the Adjustment
Level.
1. Press the L Key for less than 1 second to move from the Operation Level
to the Adjustment Level.
2. Press the M Key repeatedly to select the Hysteresis (Heating) parameter.
3. Use the U and D Keys to set the value to 2.00.
4. Press the L Key repeatedly (less than 1 second each time) to return to the
Operation Level.