Alarm Set Setting Level (L.alm) - Omron E5AR-T User Manual

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

CH
Display Alarm Setting Level
Function
Setting
Reference
Reference
CH
Alarm Set * Alarm Value 1
Alarm Set * Alarm Value 2
Alarm Set * Alarm Value 3
Alarm Set * Alarm Value 4
(*: 1 to 4)
Function
Setting
Reference
Reference
d.alm
The alarm set number for which display settings are to be made is
selected using this parameter.
• The Display Alarm Setting Level parameter is used to select the
alarm set number for which display settings are to be made.
• Up to 4 alarm sets, alarm set numbers 1 to 4, to which the alarm
values and upper/lower alarm limits have been registered, can be
used.
Setting range
1 to 4
Note:The selected and executed alarm set number.
● Related Parameters
Alarm Set Number (Program Setting Level) (P. 8-20)
*.al-1
*.al-2
*.al-3
*.al-4
The alarm values for alarms 1 to 4 can be registered for each alarm
set.
• The Alarm Set 1 to 4 Alarm Value 1 to 4 parameters are used to set
the alarm values.
• These parameters can be set when the Alarm Type parameter is set
to a value other than "No alarm", "Upper- and lower-limit alarm",
"Upper- and lower-limit of range alarm", and "Upper- and lower-limit
alarm with standby sequence".
Setting range
−19999 to 99999
● Related Parameters
Alarm * Type (Alarm Setting Level) (P. 8-75)
Alarm * Latch (Alarm Setting Level) (P. 8-76)
Alarm * Hysteresis (Alarm Setting Level) (P. 8-77)
Standby Sequence Reset (Alarm Setting Level) (P. 8-78)
Auxiliary Output * Open in Alarm (Alarm Setting Level) (P. 8-79)
Alarm SP Selection (Expansion Control Setting Level) (P. 8-97)

8.7 Alarm Set Setting Level (l.alm)

Alarm function enabled
Unit
Default value
(See note.)
Alarm function enabled
Unit
Default value
EU
0
l.alm
l.alm
8-37