Section 4 Settings Required for Basic Control

■ Changing Parameters

Parameter changes forward
after M key is pressed for less than 1 second.
After pressing
M key

■ Saving Parameter Settings

4-4
Within each level, the parameter will change either forward or
backward each time the M Key is pressed. (The parameters will not
change backward in the Calibration Level.) For details, refer to
Section 8 Parameters.
Parameter 1
M
Parameter 2
M
Parameter 3
Hold down the M key.
Parameter 4
• The first parameter will be displayed if the M Key is pressed when
the last parameter is being displayed.
• To change a setting, use the U and D Keys to change the setting
and then either wait for 2 seconds or press the M Key to save the
change.
• A change to a parameter setting is also saved when the level is
changed.
• Before turning OFF the power supply, always be sure that any
changes to parameter settings are confirmed (e.g., by pressing the
M Key). Any changes made with the U and D Keys that have not
been saved will be lost when the power supply is turned OFF.
Parameter changes backward every
second when the M key is held down.
Parameter 2
After holding down
M key for 2 seconds
Parameter 3
After holding down
M key for 1 second