Section 3 Typical Control Examples

■ Settings

● Setting Procedure
Input initial Setting Level
i1-t
2
l.0
amoV
Move to Advanced
Function Setting Level
0
-169
l.0
ch-n
Number of
Enabled Channels
4
3
l.adf
3-8
Inputs 1, 2 and 3 are set for type-K thermocouples. The settings for
input 1 are shown below. The same settings are used for inputs 2 and
3.
Type
Input 1 type switch
(Same for inputs 2 and 3.)
Input 1 Input Type parameter
(Same for inputs 2 and 3.)
Number of Enabled Channels parameter 3
1. Hold down the L Key for at least 3 seconds to move from the Operation
Level to the Input Initial Setting Level. i1-t (Input 1 Input Type) will be
displayed. Press the U Key to select the setting 2 (K 200.0 to 1300.0°C)
2. Press the M Key repeated to select amov (Move to Advanced Function
Setting Level). Press the D Key and set the password to -169 to move to
Advanced Function Setting Level.
3. Press the M Key repeated to select ch-n (Number of enabled channels).
Press the D Key to set the number of enabled channels to 3. This will
disable channel 4.
4. Press the L Key twice for at least 1 second to return to the Input Initial
Setting Level, and then press the L Key for at least 1 second to return to
the Operation Level.
Input the program for channel 1 according to the setting procedure in
3.1 Standard Control (P. 3-2).
Setting
TC. PT (factory setting)
2: K, 200.0 to 1300 C (default)