Section 5 Functions and Operations

■ Segment Outputs

5-34
SP
Time signal
output
• The Time Signal 1 Set Segment 1 to Time Signal 6 Set Segment 3
parameters are used to set the segments in which the time signals
will start. The default setting is 0 (disabled).
• The ON/OFF timing is set using the Time Signal 1 ON Time 1 to
Time Signal 6 ON Time 3 and Time Signal 1 OFF Time 1 to Time
Signal 6 OFF Time 3 parameters. The default setting is 0.00 or
0.00.0.
• Set the interval between the switch-ON time and switch-OFF time to
at least 100 ms. Unexpected operation may result if the interval is
less than 100 ms.
• ON Conditions
• If the switch-OFF time is shorter than the switch-ON time, the
output remains ON from when the switch-ON time has elapsed
until reset or the next program starts.
• If an advance operation is executed during a segment where a
time signal is set, a time equivalent to the segment will be
considered to have elapsed. In the above diagram, for example,
outputs remain ON from the start of the next segment until the
switch-OFF time has elapsed.
• The time signal is turned OFF under the following conditions:
• During a reset
• When one program has been completed when a program repeat
or program link operation has been set.
• The time signal timer stops during hold, wait, and AT operations.
• One of following functions can be selected: Segment Output, Time
Signal, or Segment No. Output (described later).
• Up to 10 outputs can be set for each program if using segment
outputs is selected.
• Segment outputs can be set to ON or OFF for each segment.
Outputs are turned ON if the Segment Output parameter for that
segment is set to ON.
Time
ON time
OFF time