Section 5 Functions and Operations
Input Value 2 for
Input Correction
.
Input Value 1 for
Input Correction
.
● Example of 2-point
Correction
Input Value 1 for Input Correction
i5i.1
40.0
l.adj
Input Shift 1
i55.1
-15.00
l.adj
Input Value 2 for Input Correction
i5i.2
500.0
l.adj
Input Shift 2
i55.2
50.00
l.adj
5-4
Temperature indicated on Controller (A)
Indicated temperature
after adjustment
(e.g., 550.0 C)
=
Indicated temperature
before adjustment
(e.g., 500.0 C)
Indicated temperature
before adjustment
=
(e.g., 40.0 C)
Indicated temperature
after adjustment
(e.g., 25.0 C)
Room temperature
(e.g., 25 C)
The following example for a K typing input (1) from 200 to 1300°C.
• The temperature of the object is obtained.
At room temperature ((B) = 25°C),
the Controller reading is
Near the SP ((B) = 550°C),
the Controller reading is
• In this case, the input correction values are obtained as follows:
Input Value 1 for Input Correction = Controller reading (A) = 40.0 (°C)
Input Correction 1
= Temperature of object (B)
= 25
40 = 15.00 (°C)
Input Value 2 for Input Correction = Controller reading (A) = 500.0 (°C)
Input Correction 2
= Temperature of object (B)
= 550
500 = 50.00 (°C)
Input Correction 2
Input Correction 1
.
Near SP
(e.g., 550 C)
Figure 2. Two-Point Correction
(A) = 40.0°C
(A) = 500.0°C
Controller reading (A)
Controller reading (A)
After correction
Before correction
.
Temperature
indicated on
thermometer (B)