■ Other

The ramp slope of the immediately preceding ramp segment is
continued even if the program direction (temperature increasing/
decreasing) is different from the ramp segment.
If an input error occurs when power is restored, the program moves to
the next segment.
The program timer value is held until the program returns to the status
before the power was interrupted.
• Power Interrupted in Fixed SP or Remote SP Mode
Ramp operation is not executed for a fixed SP or remote SP if the
power is interrupted in Fixed SP Mode or Remote SP Mode.
• The timer continues when the mode is changed to Manual Mode
during program operation.
• The timer continues if an input error occurs during program
operation.
• In setting area 1, the time signal, segment output, program end
output, and segment number output are all OFF.
• The program operation is also reset if the Run/Reset parameter for
the secondary side (channel 2) is set to "Reset" when using cascade
control.
4.12 Starting and Stopping Operation