Omron E5AR-T User Manual page 256

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

CH
Segment Output*
(*: 1 to 10)
Function
Setting
Reference
Reference
CH
PID Set Number
Function
Setting
Reference
Reference
sgo.*
• This parameter is used to turn auxiliary outputs ON or OFF for the
specified segment.
Setting range
off
: Segment output OFF
on
: Segment output ON
● Related Information
Segment Outputs in 5.7 Program Operation Functions (P. 5-34)
● Related Parameters
Auxiliary Output * Assignment (Control Initial Setting 2 Level) (P. 8-
67)
Program Output Selection (Control Initial Setting 2 Level) (P. 8-68)
pid
• This parameter is used to set the PID set number for each program.
• When this parameter is set to 0, the PID set number is automatically
selected using the PID Set Automatic Selection function and based
on the present value (PV), deviation (DV), and present SP (SP). The
PID set number can be set between 1 and 8.
• If this parameter is set to 0 for channels 2 to 4 when using coordi-
nated operation or for the secondary side (CH2) when using
cascade control, the PID set number selected for channel 1 will be
used for the other channels.
For example, if the channel 1 PID set number is set to 0, the PID set
for each channel (i.e., channels 2 to 4) will be selected automatically.
Setting range
0 to 8
● Related Information
PID Sets in 5.2 Control Functions (P. 5-10)
8.4 Program Setting Level ( )
CH1 or CH2 for independent operation with
the Segment Output parameter enabled
Unit
off
-
Unit
-
0
Default value
Default value
8-19