Hold - Omron E5AR-T User Manual

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

Section 6 CompoWay/F Communications
Response

■ Hold

Command
6-34
Related
information
Ch
"31"
4
"32"
"F1"
All
"F2"
Use this command to select the SP Mode. Refer to SP Modes in 5.7
Program Operation Functions (P. 5-31) for details on the SP Mode.
This command can be used in both setting area 0 and setting area 1.
• If AT is being run in the specified channel, an operation error will
occur.
To use this command, the communications writing function must be
enabled using the Communications Writing operation command.
MRC
SRC
Response code
"30"
"05"
"0000"
Response Codes:
The response for a normal end is shown above. For the
response codes, refer to 6.7 Operation Commands (P. 6-13).
Instruction
Related
MRC
SRC
code
information
"30"
"05"
"12"
Related
information
Ch
"00"
1
"01"
"10"
2
"11"
"20"
3
"21"
"30"
4
"31"
"F0"
All
"F1"
Description
Command mode
Remote SP
Fixed SP
Remote SP
Fixed SP
Description
Command mode
Hold Cancel
Hold
Hold Cancel
Hold
Hold Cancel
Hold
Hold Cancel
Hold
Hold Cancel
Hold

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5er-t

Table of Contents