Section 10 Troubleshooting

■ SP Does Not Change as Programmed

Remote SP Mode or Fixed SP Mode is set.

■ The Segment Does Not Advance

The wait operation is enabled.
The SP is being held.

■ The Program Is Reset in the Middle

The Number of Segments Used parameter is set to
a smaller value than the final segment number.
10-8
Possible cause
Possible cause
Possible cause
Solution
Set Program SP Mode.
Solution
Set the Wait Mode, Wait Band Upper Limit, and
Wait Band Lower Limit correctly.
Check the HOLD indicator. If it is lit, change the
Hold parameter to "OFF."
Solution
Correct the setting of the Number of Segments
Used parameter.