Section 8 Parameters
CH
PID Automatic Selection Range Upper Limit
( : 1 to 8)
Function
Setting
Reference
Reference
8-42
When using automatic selection of PID sets, use these parameters to
set an upper limit for each PID set.
• Set the automatic selection range upper limit for PID Sets 1 to 8.
• The limit for PID Set 8 is fixed at 110% of the sensor setting range,
and thus does not need to be set.
• These upper limits are applied to the PV (present value), DV
(deviation), or SP (present SP) set in the PID Set Automatic
Selection Data parameter. The default setting is "PV."
Setting range
19999 to 99999
● Related Information
PID Sets in 5.2 Control Functions (P. 5-10)
● Related Parameters
PID Set Automatic Selection Data (Expansion Control Setting Level)
(P. 8-98)
.aut
Unit
EU
1450.0
l.pid
Default value