■ Wiring

■ Settings

● Setting Procedure
Input 1 Input Type Switch
TC.PT
IN1
TYPE
ANALOG
Input Initial Setting Level
Input 1
i1-t
Input Type
2
11
U
l.0
A type-R thermocouple is connected to the IN1 terminal, and an SSR
is connected to the OUT1 terminal. The wiring for the E5AR-TQ4B is
shown in the following diagram.
100 to 240 V AC
Sensor
Heater
G3PB
SSR
Set the parameters as follows:
Parameter
Input 1 type switch
Input 1 Input Type
Output 1 Type
Control Mode
Direct/Reverse Operation
PV Start
End Condition
Control Period (Heating)
1. Before turning ON the power, be sure that the input 1 type switch is set to
TC. PT.
2. Turn ON the power and then hold down the L Key for at least 3 seconds to
move from the Operation Level to the Input Initial Setting Level. i1-t
(Input 1 Input Type) will be displayed. Press the U Key to select the setting
11 (R 0.0 to 1700.0°C).
3.1 Standard Control
E5AR-T
A
B
C
1
2
3
4
5
6
1
2
3
4
5
OUT1
6
F
G
H
I
Setting
TC. PT (default )
11 (R 0.0 to 1700.0°C)
0 (Pulse Voltage Output (default))
0 (Standard Control (default))
or-r (Reverse Operation (default))
sp (SP Start (default))
cont (Continue (default))
2.0
D
E
1
2
3
4
5
6
1
2
3
4
IN1
5
6
J
K
3-3