Back; Echoback Test - Omron E5AR-T User Manual

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

■ Back

Command
Response

■ Echoback Test

Command
Response
Slave
Function
Write start
Operation
address
code
address
code
H'06
H'00
H'00
H'14
1
1
2
Related
information
Ch
"00"
1
"10"
2
"20"
3
"30"
4
"F0"
All
This command executes a back operation. Operation will move to the
beginning of the current segment.
This command is used in setting area 0. An operation error will occur if
it is used in setting area 1.
Operation errors will also occur in the following cases:
• If AT is being executed
• If the specified channel is being reset or is on standby
To use this command, the communications writing function must be
enabled using the Communications Writing operation command.
Slave
Function
Write start
Operation
address
code
address
code
H'06
H'00
H'00
H'14
1
1
2
The response for a normal end is shown above. For information on
error responses, refer to 7.7 Operation Commands (P. 7-15).
Slave
Function
Write start
address
code
address
Test data
H'08
H'00
H'00
1
1
2
This command is used to perform an echoback test.
The command can be used in any state of the E5AR-T/ER-T.
The test data can be any two bytes of hexadecimal data.
Slave
Function
Write start
address
code
address
Test data
H'08
H'00
H'00
1
1
2
The response for a normal end is shown above. For information on
error responses, refer to 7.7 Operation Commands (P. 7-15).
7.9 Commands and Responses
Related
information
CRC-16
2
2
Description
Command mode
Back
Back
Back
Back
Back
Related
information
CRC-16
2
2
CRC-16
2
2
CRC-16
2
2
7-35

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5er-t

Table of Contents