Section 5 Functions and Operations
● Standby

■ End Condition

5-38
• When a standby is set, the program does not start operating until the
standby time (set in hours:minutes) has elapsed after the Run/Reset
parameter is set to "Run."
• The following conditions apply to operation during a standby:
• Control outputs are governed by the MV at Reset parameter (the
indicators and status display will show Run status).
If the Operation at Reset parameter is set to "Fixed Control," then
control outputs will start from the fixed SP.
• Hold, advance, back, and AT operations (when the Operation at
Reset parameter is set to "Stop Control") cannot be executed.
If AT is executed when the Operation at Reset parameter is set to
"Fixed Control," the remaining standby time during AT execution is
held.
• If the power is interrupted during a standby, the remaining standby
time is held (if the Operation at Power ON parameter is set to
"Continue," if the program is running and in Manual Mode before
the power was turned OFF, and if a ramp back is set.
• If run operation is executed in reset status, the remaining standby
time is set as the value for the Standby Time parameter. This means
the remaining standby time is continued when run operation is
executed during a standby (the set value for the Standby Time
parameter is not initialized).
The End Condition parameter is used to select the operation after a
program has been completed can be selected. The options are Reset
Status, Continue, or Fixed SP Mode
Operating
status
Reset status
Ends operation.
Continue
Control is continued using the SP of the last segment.
The final segment number is held as the segment number
and the elapsed program time, elapsed segment time, and
remaining segment time are held.
The time signal status at the end of operation is held.
If the setting of the Number of Segments Used parameter is
changed after operation has completed, there is no change to
the operation end status but control will switch to using the
SP of the last segment after the change.
Fixed SP
Operation is continued in Fixed SP Mode after the program
Mode
has completed (run status).
The segment number, elapsed program time, elapsed seg-
ment time, and remaining segment time will be the values
from the start of the program.
The time signal is OFF.
If the SP Mode parameter is changed to Program SP (PSP),
the program will start again.
If, however, the Operation at Reset parameter is set to "Fixed
Control," Fixed SP Mode cannot be set.
.
Description