CH
Alarm SP Selection
Function
Setting
Reference
Reference
Program End ON Time
Function
Setting
Reference
Reference
8.18 Expansion Control Setting Level (l.exc)
alsp
• This parameter is used to select whether the alarm value deviation
will be based on the present SP or the target SP.
Setting range
psp: Present SP
tsp: Target SP
● Related Information
Alarm SP Selection in 5.6 Alarm Adjustment Functions (P. 5-26)
● Related Parameters
Alarm Set * Alarm Value * (Alarm Set Setting Level) (P. 8-37)
Alarm Set * Alarm Upper Limit * (Alarm Set Setting Level) (P. 8-38)
Auxiliary Output * Assignment (Control Initial Setting 2 Level)
(P. 8-67)
Alarm * Type (Alarm Setting Level) (P. 8-75)
Alarm * Latch (Alarm Setting Level) (P. 8-76)
Alarm * Hysteresis (Alarm Setting Level) (P. 8-77)
Standby Sequence Reset (Alarm Setting Level) (P. 8-78)
pend
• This function is used to set the pulse width for program end output.
• The setting range is ON, 0.0 to 10.0 s. The default is 0.0.
• When this parameter is set to ON, the ON status continues during a
reset until operation starts.
Setting range
on: Continue ON output
0.0: No output
0.1 to 10.0
● Related Information
Program Status Outputs in 5.7 Program Operation Functions (P. 5-
36)
● Related Parameters
Auxiliary Output * Assignment (Control Initial Setting 2 Level) (P. 8-
67)
Alarm Type 1 to 4 parameters set to
Unit
Default value
psp: Present SP
Unit
Default value
s
0.0
l.exc
"Deviation Alarm"
l.exc
8-97