Alarm
Type
: 1 to 4)
Function
Setting
Reference
Reference
alt*
• These parameters are used to select the alarm types for alarms 1
through 4.
Setting range
0: No alarm function
1: Upper- and lower-limit alarm
2: Upper limit alarm
3: Lower limit alarm
4: Upper- and lower-limit range alarm
5: Upper- and lower-limit alarm with standby
sequence
6: Upper limit alarm with standby sequence
7: Lower limit alarm with standby sequence
8: Absolute-value upper-limit alarm
9: Absolute-value lower-limit alarm
10: Absolute-value upper-limit alarm with standby
sequence
11: Absolute-value lower-limit alarm with standby
sequence
● Related Parameters
Alarm Set
Alarm Value
Alarm Set
Alarm Upper limit
Auxiliary Output
Assignment (Control Initial Setting 2 Level)
(P. 8-67)
Alarm
Latch (Alarm Setting Level) (P. 8-76)
Alarm
Hysteresis (Alarm Setting Level) (P. 8-77)
Standby Sequence Reset (Alarm Setting Level) (P. 8-78)
Alarm SP Selection (Expansion Control Setting Level) (P. 8-97)
8.14 Alarm Setting Level (l.3)
Alarm set for Auxiliary Output
Assignment parameter
Unit
(Alarm Set Setting Level) (P. 8-37)
(Alarm Set Setting Level) (P. 8-38)
l.3
Default value
2: Upper limit
alarm
8-75