Section 9 User Calibration
adj
30
l.cal
Input types 2, 4, 7, 8, 10, 14
1t53.1
d72b3
l.cal
Input types 3, 5, 6, 9, 11, 12, 13
Input types 3, 5, 6, 9, 11, 12, 13
Input types 3, 5, 6, 9, 11, 12, 13
2t22.1
2t22.1
2t22.1
c8496
c8496
c8496
l.cal
l.cal
l.cal
Input types 2, 4, 7, 8, 10, 14
1e-6.1
76196
l.cal
9-6
Follow these steps to perform calibration when thermocouple input is
selected.
1. Connect the power supply.
2. Connect the DC reference current/voltage generator (STV below),
precision digital meter (DMM below), and cold junction compensator (a
ZERO-CON is used as an example below) to the input terminals of the
thermocouple as shown below.
STV
DMM
Leave open.
ZERO-CON
OUTPUT
INPUT
3. Turn ON the power.
4. Move to Calibration Level.
A 30-minute aging timer will begin. Perform aging using this timer as a
guideline. When 30 minutes has elapsed, Display No. 2 will show 0.
You can proceed to the next stop before the display shows 0.
5. Press the M Key. The display at the left will appear.
The count value that was input will be displayed on Display No. 2 in
hexadecimal. Set the STV as follows:
• For input types 2, 4, 7, 8, 10, and 14: 53 mV
• For input types 3, 5, 6, 11,12, and 13: 22 mV
Wait until the count on Display No. 2 is sufficiently stable and then press
the D Key. This tentatively registers the calibration data at this point.
6. Press the M Key. The display at the left will appear.
Set the STV to 6 mV.
Wait until the count on Display No. 2 is sufficiently stable and then press
the D Key. This tentatively registers the calibration data at this point.
_
+
Compensating leads of selected thermocouple
However, compensating leads for a K thermocouple
can be used for E, R, S, B, and W thermocouples.