Section 7 Modbus Communications

7.4 Variable Areas

The areas used for data exchange when communicating with the E5AR-T/ER-T are called the variable
areas. Present values can be read, and set values can be read and written using the variable areas of the
E5AR-T/ER-T.
Operation commands do not use the variable areas.

■ Addresses

● Area Numbers
7-8
Operation
commands and
responses
Read/write
Personal computer
A variable area is accessed by specifying the position of a variable
within the variable area using the channel identifier, area number, and
address in the area.
Addresses are allocated within each variable type. Addresses are two
bytes long and written in hexadecimal. Addresses are allocated
according to access size. Each address consists of a channel
identifier, area number, and the address in the area.
Address (2 bytes)
Channel
Area number (00 to 3F)
(0 to 3)
Area numbers in the variable area are listed in the following table.
Variable
type
04
Communications Monitor
05
Protect Level
06
Operation Level
07
Adjustment Level
08
Adjustment 2 Level
09
Alarm Set Setting Level
0A
PID Setting Level
0B
Approximation Setting Level
18
Program Setting Level
19
Time Signal Setting Level
E5AR/ER-T
Microprocessor
Variable area
0
A6
A5
A4
A3
A2
A1
A0
Address in area (00 to FE)
Description
Area
Setting area 0
(Operation in
progress.)