Omron E5AR-T User Manual page 350

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

Input types 15 and 16
a
1.1
85490
l.cal
Input types 17 and 18
1V 1.1
952c3
l.cal
Input type 19
2V 1.1
8a95b
l.cal
str.i1
no
l.cal
7. Press the Key M. The display at the left will appear.
Set the STV as follows:
• Input types 15 and 16:
• Input types 17 and 18:
• Input type 19:
8. Wait until the count on Display No. 2 is sufficiently stable and then press
the D Key. This tentatively registers the calibration data at this point.
9. Press the M Key. The display at the left will appear. This display will not
appear if all of the required data has not been tentatively registered.
Press the U Key. Display No. 2 will show yes. Two seconds after the Key
is released or when the M Key is pressed, the tentatively registered
calibration data will be stored in EEPROM. If you do not wish to save the
data in EEPROM, press the M Key instead of the U Key.
• For a Controller with more than one input, connect as explained in step 2
and repeat steps 5 to 9.
• If linear current output is selected, continue with the procedure in 9.6
Output Calibration (P. 9-12).
10. Turn OFF the power to leave Calibration Mode.
9.4 Analog Input Calibration
1 mA
1 V
1 V
9-9