Omron E5AR-T User Manual page 68

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

Set value
Input type
15
4 to 20 mA
16
0 to 20 mA
17
1 to 5 V
18
0 to 5 V
19
0 to 10 V
Set the input type switch according to the setting of the Input Type parameter.
The default settings are 2 and TC.PT.
■ Scaling
25.0
0.0
01.01
i1-t
15
l.0
inp.1
5
l.0
dsp.1
0
l.0
inp.2
20
l.0
dsp.2
1000
l.0
Setting range
(°C)
One of the following ranges is displayed depending
on the scaling.
19999 to 99999
1999.9 to 9999.9
199.99 to 999.99
19.999 to 99.999
1.9999 to 9.9999
When an analog input (voltage or current input) is used,
Hint
scaling is possible according to the type of control.
Setting the Display to Show 0.0 for an Input Value of 5 mA and 100.0
for 20 mA When the Input 1 Type Parameter Is Set to 4 to 20 mA.
1. Hold down the L Key for at least 3 seconds to move from the Operation
Level to the Input Initial Setting Level.
2. Make sure that i1-t (Input 1 Type) is set to 15 (4 to 20 mA).
3. Press the M Key repeatedly to select inp.1 (Scaling Input Value 1).
Set the scaling input value to 5 with the U and D Keys.
4. Press the M Key to select dsp.1 (Scaling Display Value 1).
Set the scaling display value to 0 with the U and D Keys.
5. Press the M Key to select inp.2 (Scaling Input Value 2).
Set the scaling input value to 20 with the U and D Keys.
6. Press the M Key to select dsp.2 (Scaling Display Value 2).
Set the scaling display value to 1000 with the U and D Keys.
4.4 Setting the Input Type
Input type
switch
(°F)
ANALOG
TC.PT
IN1
TYPE
ANALOG
4-11

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5er-t

Table of Contents