● Operation at Reset
Parameter Set to
Use Fixed Control
SP
Seg-
Segment 2
Segment 4
ment 1
200.0
150.0
100.0
30.0
6:00
10:00
• For the E5AR-T/ER-T, Step Time programming is used for segment
1. The rate of rise programming can be selected to start from the
segment 1 SP or from a PV start with slope priority.
• With rate of rise programming, the settings are made in blocks of
two segments, so the final soak time cannot be set if the Number of
Segments Used parameter is set to an even number. Therefore, the
final segment will be a soak segment if the Number of Segments
Used parameter is set to an odd number and will be a ramp segment
if set to an even number.
Ramp settings are made for odd-numbered segments by setting the
SP and rate of rise.
• The following table shows a setting example. The Time Unit of Ramp
Rate parameter is set to "Time."
Segment No.
1
Segment Set
100.0
Point
Segment Rate of
7.0
Rise
Segment Time
---
(hours:minutes)
Segment 1
SP
200.0
150.0
100.0
FSP
(=30.0)
10:00
5.7 Program Operation Functions
Segment 5
Segment 6
20:00
14:00
2
3
4
---
200.0
---
---
5.0
---
0:00
---
14:00
Segment 4
Segment 3
20:00
14:00
10:00
Time (h:min)
5
• • •
150.0
• • •
5.0
• • •
---
• • •
Segment 5
10:00
Time (h:min)
5-29