Omron E5AR-T User Manual page 306

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

Transfer Output
Upper Limit
Transfer Output
Lower Limit
( : 1 to 4)
Function
Setting
Reference
Reference
trh.
trl.
• These parameters can only be used for outputs selected for transfer
output using the output assignment parameters.
Control/
Transfer output
Setting range
assignment
data
SP lower limit to
Present set point
SP upper limit
Lower limit of
sensor setting
range to upper
limit of sensor
setting range
PV
(temperature)
19999 to 99999
(analog)
Standard: -5.0 to
Control output
105.0; Heating/
(heating or
cooling: 0.0 to
open)
105.0
Control output
(cooling or
0.0 to 105.0
close)
Valve opening
10.0 to 110.0
* The parameters will be initialized if the input type, temperature
units, scaling display value, SP upper and lower limits, or applicable
control/transfer output assignment is changed.
● Related Information
5.9 Using a Transfer Output (P. 5-47)
● Related Parameters
Input
Type (Input Initial Setting Level) (P. 8-50)
Control/Transfer Output
Level) (P. 8-64)
8.13 Control Initial Setting 2 Level (l.2)
Transfer output using output assignment
Default value
(upper limit/
Decimal
lower limit of
transfer
position
output) *
Depends
1300.0 and
on input
200.0
type
Upper and
Depends
lower limit of
on input
sensor setting
type
range
Scaling
Depends
display value 2
on input
and 1
type
100.0 and 0.0
1
100.0 and 0.0
1
100.0 and 0.0
1
Assignment (Control Initial Setting 2
l.2
point
units
EU
EU
EU
%
%
%
8-69