■ Disturbance Overshoot Adjustment

Disturbance Overshoot
Adjustment Function
1
dost
on
l.exc
● Disturbance Gain

Disturbance Gain

1
dogn
0.65
l.adj
● Disturbance Time
Constant
Disturbance Time Constant
1
dotc
1.00
l.adj
• The disturbance overshoot adjustment function adjusts the control
waveform when disturbance occurs.
• To use this function, set the Disturbance Overshoot Adjustment
Function parameter to "ON" (the default setting is "OFF").
• The disturbance response waveform can be adjusted using the
Disturbance Gain and Disturbance Time Constant parameters.
• The Disturbance Gain parameter can be increased to reduce
overshooting when disturbance occurs.
• The Disturbance Gain parameter can be decreased to increase
overshooting when disturbance occurs.
• When the Disturbance Gain parameter is set to 0, the disturbance
overshoot adjustment function does not operate.
Temperature
SP
0
• The reset time after disturbance can be lengthened by increasing
the disturbance time constant. (The default value of 1 is normally
used for the disturbance time constant. If adjustment of the distur-
bance gain alone is not sufficient, this value can be adjusted for fine-
tuning.)
Temperature
SP
0
• The waveform may vary from that in the diagram depending on
differences in the object of control and differences in PID constants.
5.2 Control Functions
When disturbance gain is 1
When disturbance gain is 0.5
When disturbance gain is 0
When disturbance gain is 0.5
When disturbance gain is 1
Time
When disturbance time constant is 1
When disturbance time constant is 2
Time
5-13