8.3 Operation level

Display this level to operate the control system. The SP can be set and the PV monitored in this level.
Power on
Adjustment

Operation level

level
L key less
than 1 second
L key less
than 1 sec
Approximation
PID setting
setting
level
level
l. tec
L key less
than 1 second
CH
Manual MV
Function
(
)
Adjustment 2
level
l. adj
l. ad2
L key less
than 1 second
L key less
than 1 second
Bank setting
level
l. pid
l. bnk
L key less
than 1 second
Control in
progress
Operation Level
CH
25
manu
CH
25
bnk. 0
CH
25
CH
25
bnk.0
CH
rsp
CH
sp-m
• This sets the MV or valve opening during manual operation. On a
standard type the MV is changed by pressing the UD keys. On a
position proportional type, the U key turns on "open" and the D key
turns on "close".
• On a standard type Display 1 shows the PV and Display 2 shows the
MV.
0
PV / manual MV
.
(Position proportional control type:
0.0
1
PV / valve opening)
M
0
.
PV / SP (display 1)
0.0
PV / SP / bank No.
M
PV / SP (display 2)
0
.
Present / SP /
2
0.0
MV
0.0
M
0
PV / SP (display 3)
.
Present / SP / bank No.
0.0
M
RSP: Remote SP monitor
0.0
M
SP-M: Ramp SP monitor
0.0
M
8.3 Operation level ( )
M
CH
o
O: MV monitor (heating)
0.0
M
CH
c-o
C-O: MV monitor (cooling)
0.0
M
CH
-m
V-M: Valve opening monitor
0.0
M
CH
r-s
R-S:RUN/STOP
run
M
CH
a-m
A-M:AUTO/MANU
auto
M
1 In manual mode
2 One of the following is displayed depending on
the "Display screen selection" setting:
Display 1 / Display 2
Display 2 / Display 3
Display 1 only
Display 2 only
manu
Manual operation